6.7.3 Setting the highest station number for a PLC link

Sample settings
FP0R User's Manual
Send area is split
Send and receive areas are split into multiple segments
Send area
Station numbers should be set sequentially and consecutively, starting
from 1, with no breaks between them. If there is a missing station number,
or if there is a station for which the power supply has not been turned on,
the response time for the PLC link (the link transmission cycle time) will be
longer (see p. 155).
If there are fewer than 16 stations linked, set the highest station number
to reduce the link transmission cycle time. (The default value is 16.) Set
the same value for all PLCs in the link.
The highest station number is set using system register no. 47 for PLC link
0 or system register no. 57 for PLC link 1.
Total number of stations:
Station number:
Highest station number