COM port (RS232C)
COM port (RS485)
FP0R User's Manual
Item
Interface
Transmission distance
Baud rate
Communication method
Synchronous method
Communication format
Data transmission order
Communication mode
Item
Interface
Connection mode
Transmission distance
Baud rate
Communication method
Synchronous method
Transmission line
Transmission
MEWTOCOL-COM
code
Program controlled ASCII, Binary
Modbus RTU
Communication format (set in
4)
system registers)
No. of connected stations
Communication mode
1)
The number of stations, transmission distance, and baud rate may vary de-
pending on the connected RS485 device.
Description
RS232C
15m
2400, 4800, 9600, 19200, 38400, 57600, 115200bit/s
Half-duplex
Start stop synchronous system
Data length: 7 bits/8 bits
Parity: None/Odd/Even
Stop bit: 1 bit/2 bits
End code: CR/CR+LF/None/ETX
Start code: No STX/STX
Transmits from bit 0 character by character.
MEWTOCOL-COM Master/Slave
Modem connection
Program controlled
Modbus RTU Master/Slave
PLC Link
Description
RS485
1:N
1)2)
1200m
19200, 115200bit/s
2-wire, half-duplex
Start stop synchronous system
Shielded twisted-pair cable or VCTF
ASCII
Binary
Data length: 7 bits/8 bits
Parity: None/Odd/Even
Stop bit: 1 bit/2 bits
End code: CR/CR+LF/None/ETX
Start code: No STX/STX
2) 5)
99 (32 with C-NET adapter)
MEWTOCOL-COM Master/Slave
Modem connection
Program controlled
Modbus RTU Master/Slave
PLC Link
Appendix
2)3)
235

Hide quick links: