COM Port
Name Name
412
COM port 1 - communication mode
410
COM port 1 -station number
415
COM port 1 - baud rate
413
COM port 1 - sending data length
413
COM port 1 -sending parity check
413
COM port 1 - sending stop bit
413
COM port 1 - sending start code
413
COM port 1 - sending end
code/reception done condition
416
COM port 1- -receive buffer starting
address
417
COM port 1 - receive buffer capacity
412
COM port 1 - modem connection
1)
For PLC Link, the communication format and baud rate settings are fixed:
Data length:
8 bits
Parity:
Odd
Stop bit:
1 bit
End code:
CR
Start code:
No STX
Other system register settings will be ignored.
FP0R User's Manual
Default
MEWTOCOL-COM
Master/Slave
1
1)
9600 baud
8 bits
1)
Odd
1 bit
1)
No-STX
CR
1)
0
0
Disable
Values
MEWTOCOL-COM Mas-
ter/Slave/Program controlled/PLC
Link/Modbus RTU Master/Slave
1–99
115200/57600/38400/19200/9600/4
800/2400 baud
7 bits/8 bits
None/Odd/Even
1 bit/2 bits
No-STX/STX
CR/CR+LF/ETX/None
0–12312 (16k type)
0–32762 (32k type)
0-2048
Disable/Enable
Appendix