Active Alarms

EATON Power Xpert
®
Gateway Series 1000 Card User's Guide
If active alarms are present in the PDU/RPP/RPM, the "(Alarms
Present)" message appears at the top of the card's data display Web
pages and data values are highlighted in red text when they are in alarm
state.
To view a list of active alarms:
1.
From the card's Web page, click the Active Alarms link from the
menu bar.
The active alarms display with the following information:
S
Time and date when the error occurred.
S
The alarm message that appears on the PDU/RPP/RPM display.
S
The parameter that is in alarm (appears as a link).
S
The alarm level (informational, critical, or major).
S
The condition of the alarm (active is true, inactive is false).
2.
To view the specific alarm parameter data, click the parameter link.
The data display page appears and the value in error appears in red
text.
NOTE In the following steps, you are prompted to enter a note regarding the alarms. This
note is optional and is entered into the Event log and appears in the Power Xpert software. If
you select Cancel to close the note window, the alarm moves to the acknowledge state
without a note.
NOTE If you select Acknowledge All or Close All, you can enter one note regarding all of
the alarms.
3.
To acknowledge that you are aware of the alarm, click Acknowledge.
To acknowledge all alarms at one time, click Acknowledge All at the
top of the page.
4.
To close the alarm and remove it from the Active Alarms list, click
Close.
To close all alarms at one time, click Close All at the top of the page.
OPERATION AND MAINTENANCE
S
www.eaton.com/powerquality
164201670 Rev 4
83