MODBUS REGISTERS

EMP (FC 04)

Table 9. EMP Registers (FC 04)
Name
Vendor Name
Model Name
Display Name
Serial Number
Device ID
Auxiliary Input 1
Auxiliary Input 2
Auxiliary Temperature
Auxiliary Humidity
74
EATON Power Xpert
The optional EMP for the PDU/RPP/RPM can measure temperature and
humidity. Because the device can be located outside the
PDU/RPP/RPM, the reference is to "auxiliary" data. In addition, it
contains two connections for monitoring the condition of auxiliary input
contacts, such as a door switch. See Table 9 for a list of EMP registers.
An exception code is returned if the EMP is not installed.
To read the temperature at the PDU/RPP/RPM, set the Modbus program
to Unit ID 254 and coil address 12028:
IP: <IP address of PDU/RPP/RPM>
Unit ID: 254
Starting Register: 12028
Number of registers: 2
Function Code: 04
Register
1032
1064
1096
1276
1192
10275
10276
12028
12030
®
Gateway Series 1000 Card User's Guide
Data Type
STRING
STRING
STRING
STRING
STRING
UINT
UINT
FLOAT
FLOAT
S
www.eaton.com/powerquality
164201670 Rev 4
Bytes
64
64
64
64
64
2
2
4
4