MODBUS REGISTERS
70
EATON Power Xpert
Table 5. Panel Summary Registers (FC 04) (continued)
Name
AC I MAX B
AC I MAX C
AC I MAX N
NOTE Only sample registers are shown. They may be different from the registers in
your PDU/RPP/RPM.

Panel Alarms (FC 02)

Table 6 lists the panel alarms. They are not registers, but are discrete
inputs and are read using FC 02.
To read the Main Breaker Overload alarm at Panel #4, set the Modbus
program to Unit ID 5 and coil address 1254:
IP: <IP address of PDU/RPP/RPM>
Unit ID: 5
Starting Register: 1254
Number of Registers: 1
Function Code: 02
Table 6. Panel Alarms (FC 02)
Name
Neutral Overload
Panel Under Voltage
Panel Over Voltage
Panel Under Over Frequency
Branch Breaker Overload Warning
Branch Breaker Overload
Main Breaker Overload Warning
Main Breaker Overload
NOTE Only sample alarms available from the Web page are shown. They may be
different from the alarms in your PDU/RPP/RPM.
®
Gateway Series 1000 Card User's Guide
Register
Data Type
5166
FLOAT
5168
FLOAT
5170
FLOAT
Coil/Status Address
1219
1238
1242
1248
1249
1250
1253
1254
S
www.eaton.com/powerquality
164201670 Rev 4
Bytes
4
4
4
Data Type
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL