Breaker Alarms (Fc 02) - Eaton Power Xpert 1000 Series User Manual

Powerware series
Hide thumbs Also See for Power Xpert 1000 Series:
Table of Contents

Advertisement

EATON Power Xpert
®
Gateway Series 1000 Card User's Guide

Breaker Alarms (FC 02)

There are two alarms for each circuit breaker: Overload Warning and
Overload. Each alarm has a unique address similar to the data registers,
but these alarms are not data registers. The alarms are discrete inputs
and are read using FC 02 in the Modbus program.
Table 8. Breaker Alarms (FC 02)
Name
Branch Breaker 1 Overload Warning
Branch Breaker 1 Overload
Table 8 shows the alarms for Breaker #1. Determine the corresponding
alarms for other breakers by using the following formula:
Breaker #5 address = ((Breaker number – 1) x 2) + Breaker #1 address
For example, to find the Overload Warning alarm address for Breaker #5:
Breaker #5 Overload Warning
To find the Overload alarm address for Breaker #20:
Breaker #20 Overload
To read the Overload Warning alarm for Breaker #5 in Panel #8, the
Modbus program would be set as follows:
IP: <IP address of PDU/RPP/RPM>
Unit ID: 25
Starting Register: 1008
Number of registers: 1
Function code: 02
The Modbus program would return a true/false value of the Overload
Warning alarm for Breaker #5 in Panel #8 of the PDU/RPP/RPM at the
specified IP address.
Coil/Status Address
1000
1001
= ((5 – 1) x 2) + 1000
= ((4) x 2) + 1000
= (8) + 1000
= 1008
= ((20 – 1) x 2) + 1001
= ((19) x 2) + 1001
= (38) + 1001
= 1039
S
www.eaton.com/powerquality
164201670 Rev 4
MODBUS REGISTERS
Data Type
BOOL
BOOL
73

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents