Time or Date (FC 04)

EATON Power Xpert
®
Gateway Series 1000 Card User's Guide
Some PDU/RPP/RPM models support a time and/or date function. This
format has a DATE data type and contains six bytes. Each byte
represents the year, month, day, hour, minutes, and seconds (see
page 61 for more information).
To read the PDU/RPP/RPM date and time, set the Modbus program to
Unit ID 1 and register 12203:
IP: <IP address of PDU/RPP/RPM>
Unit ID: 1
Starting Register: 12203
Number of registers: 3
Function Code: 04
The PDU/RPP/RPM would return three registers containing hexadecimal
data in the ym dh ms format (for example, May 17, 2007 at 10:45 and 20
seconds).
07
05
Viewing each hex byte in decimal would yield the following data, which
is viewable as the year (07), month (05), day (17), hour (10),
minutes (45), and seconds (20):
07
05
Viewing each hex byte as two-byte unsigned integers would yield the
following data:
1797
Viewing each hex byte as binary would yield the following data:
00000111
00000101
Table 10. Time or Date Register (FC 04)
Parameter Name Display Name
mCurrentTime
Time
11
0A
2D 14
17
10
45
20
4362
11540
00010001
00001010
Register
Discrete
12203
No
S
www.eaton.com/powerquality
164201670 Rev 4
MODBUS REGISTERS
00101101
00010100
Units
Data Type
Bytes
No
DATE
6
75