System Location And System Contact; Management From An Snmp Nms - Eaton Power Xpert 1000 Series User Manual

Powerware series
Hide thumbs Also See for Power Xpert 1000 Series:
Table of Contents

Advertisement

CONFIGURING THE CARD
MIB Name
Eaton PDU MIB
Eaton EMP MIB
Eaton Alarms+Traps MIB
Eaton Object Identifier (OID)
assignments
28
EATON Power Xpert

System Location and System Contact

To set the system location and system contact:
1.
From the card's Web page, click the Network link from the menu
bar.
2.
Enter the physical location of the installed Power Distribution Unit
(PDU), Remote Monitor Panel (RPP), or Rack Power Module
(RPM)/card (sysLocation string) in the System location field. This
value also appears in the card's Web page header bar.
3.
Enter the information to identify someone to contact with questions
about this device (sysContact string) in the System contact field. For
example, type a person's name, phone number, department, e-mail
address, physical location, or combination of these items, such as
"John Smith x123".
4.
Click Apply and then OK to save the settings.

Management from an SNMP NMS

To access the PXGX Series 1000 Card via SNMP:
1.
Use these default Community strings:
GET Community string: public
SET Community string: private
2.
From the card's Web page, click the Documentation link from the
menu bar (or visit www.eaton.com/powerxpert) for the following
MIB files for the PXGX Series 1000 Card:
Filename
EATON-PDU-MIB.txt
EATON-EMP-MIB.txt
EATON-PXG-MIB.txt
EATON-OIDS.txt
®
Gateway Series 1000 Card User's Guide
Description
Meters available from the PDU/RPP/RPM,
including identification, input, output,
configuration, tests, alarms, bypass, traps,
panel data, and circuit breaker data
Meters and settings for the EMP
Alarms and notifications (traps)
Base document for all OID assignments for
Eaton's MIBs
S
www.eaton.com/powerquality
164201670 Rev 4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents