MODBUS REGISTERS
72
EATON Power Xpert
Table 7. Breaker #1 Data Registers (FC 04) (continued)
Name
AC MAX Current Phase B
AC MAX Current Phase C
Percent FL Current A
Percent FL Current B
Percent FL Current C
Watts Phase A
NOTE Only sample breaker data is shown. It may be different from the registers in your
PDU/RPP/RPM.

Calculating Breaker Register Numbers

Table 7 shows the sample register numbers for Breaker #1. There can
be many breakers in a panel. Determine the corresponding register
numbers for other breakers in the panel by using the following formula:
Breaker register # = Breaker #1 register + ((Breaker # – 1) x 200))
For example:
Breaker #2 starts at 1200:
Breaker #3 starts at 1400:
Breaker #14 starts at 3600:
This formula works for any register. For example, for Breaker #1, the
register number of "Watts Phase A" is 1055. The corresponding
address for Breaker #18 is:
®
Gateway Series 1000 Card User's Guide
Register
Data Type
1045
FLOAT
1047
FLOAT
1049
FLOAT
1051
FLOAT
1053
FLOAT
1055
FLOAT
1000 + ((2 – 1) x 200)
1000 + (1 x 200)
1000 + 200
1200
1000 + ((3 – 1) x 200)
1000 + (2 x 200)
1000 + 400
1400
1000 + ((14 – 1) x 200)
1000 + (13 x 200)
1000 + 2600
3600
1055 + ((18 – 1) x 200)
1055 + (17 x 200)
1055 + 3400
4455
S
www.eaton.com/powerquality
164201670 Rev 4
Bytes
4
4
4
4
4
4