Pdu/Rpp/Rpm Alarms (Fc 02) - Eaton Power Xpert 1000 Series User Manual

Powerware series
Hide thumbs Also See for Power Xpert 1000 Series:
Table of Contents

Advertisement

EATON Power Xpert
®
Gateway Series 1000 Card User's Guide

PDU/RPP/RPM Alarms (FC 02)

The PDU/RPP/RPM monitors the condition of several parameters and
can activate an alarm status if a parameter is out of range. For example,
if the input frequency is too high or too low, the PDU/RPP/RPM can set
the Input Frequency Fault Alarm.
To read the Input Frequency Fault Alarm, set the Modbus program to
Unit ID 1 and coil address 1008:
IP: <IP address of PDU/RPP/RPM>
Unit ID: 1
Starting Register: 1008
Number of Registers: 1
Function Code: 02
The PDU/RPP/RPM returns a single register that is a BOOL value
(0 or 1), indicating if the alarm is active or not active.
Table 4. PDU/RPP/RPM Alarms (FC 02)
Name
AC Input Over Volts
AC Input Under Volts
Input Frequency Fault
AC Output Over Volts
AC Output Under Volts
AC Output Frequency Fault
Remote EPO
Building Alarm 4
Building Alarm 3
Building Alarm 2
Building Alarm 1
Output Overload
System Bus Overload
NV Memory Failure
NOTE Only sample alarms available from the Web page are shown. They may be
different from the alarms in your PDU/RPP/RPM.
Register
S
www.eaton.com/powerquality
164201670 Rev 4
MODBUS REGISTERS
Data Type
1006
BOOL
1007
BOOL
1008
BOOL
1009
BOOL
1010
BOOL
1011
BOOL
1012
BOOL
1016
BOOL
1017
BOOL
1018
BOOL
1019
BOOL
1025
BOOL
1050
BOOL
1053
BOOL
67