Dip Switch Description - Eaton Power Xpert 1000 Series User Manual

Powerware series
Hide thumbs Also See for Power Xpert 1000 Series:
Table of Contents

Advertisement

OPERATION AND MAINTENANCE

DIP Switch Description

82
EATON Power Xpert
DIP switch definitions for the PXGX Series 1000 Card are listed in
Table 14.
Table 14. DIP Switch Definitions
S1 Position
OFF Position (Default)
Number
1
Enable previously stored
network configuration settings
(Normal mode)
2
Enable the front panel RJ-45 for
serial communication
3
Normal behavior
4
Reserved
5
Reserved
6
Normal behavior
®
Gateway Series 1000 Card User's Guide
ON Position
Override network settings to assign
private IP addresses (Configuration
mode); Port 1 is set to 192.168.1.1
and Port 2 is set to 192.168.1.2
Enable the front panel RJ-45 port for
communication with a Powerware
Environmental Monitoring Probe
(EMP) device for immediate or
future use
Reset the HTTP passwords to the
defaults on boot (user and admin).
After a successful boot, the switch
should be turned back off before
rebooting the card.
Reserved
Reserved
Reset the card to factory defaults on
boot (after a successful boot, the
switch should be turned back off
before rebooting the card)
S
www.eaton.com/powerquality
164201670 Rev 4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents