MODBUS REGISTERS

Modbus Register Addressing

60
EATON Power Xpert
This section describes Modbus function codes, data formats, and data
addressing.

Modbus Function Codes

The PDU/RPP/RPM registers are read using Modbus Function Codes
(FC). For most PDU/RPP/RPM registers, FC 04 is used. For alarms,
FC 02 is used. The PDU/RPP/RPM supports the following hex function
codes:
Table 1. Function Codes
FC
Hex
Description
01
0x01
Read Coil Status
02
0x02
Read Discrete Inputs
03
0x03
Read Holding Registers
04
0x04
Read Input Registers
05
0x05
Write Single Coil
06
0x06
Write Single Register
0F
0x0F
Write Multiple Coils
10
0x10
Write Multiple Registers
®
Gateway Series 1000 Card User's Guide
Use
Supported for compatibility purposes
Single input data, such as alarms and
discrete contacts
Supported for compatibility purposes
Analog data (most string and numeric
data types), such as voltage
For future use
For future use
For future use
For future use