Power Cable Warning (Japanese)

WARNING: The attached power cable is only for this product. Do not use the cable
for another product.

DC Power Electrical Safety Guidelines and Warnings

DC Power Electrical Safety Guidelines
The following electrical safety guidelines apply to a DC-powered router:
NOTE: Primary overcurrent protection is provided by the building circuit breaker.
This breaker should protect against excess currents, short circuits, and earth faults
in accordance with NEC ANSI/NFPA70.
148
Safety Guidelines and Warnings
A DC-powered router is equipped with a DC terminal block that is rated for the
power requirements of a maximally configured router. To supply sufficient power,
terminate the DC input wiring on a facility DC source capable of supplying at
least 13.5. The 48 VDC facility DC source should be equipped with a circuit
breaker rated at 15 minimum. Incorporate an easily accessible disconnect device
into the facility wiring. In the United States and Canada, the 48 VDC facility
should be equipped with a circuit breaker rated 75 A (-48 VDC) in accordance
with the National Electrical Code in the US and the Canadian Electrical Code in
Canada. Be sure to connect the ground wire or conduit to a solid office (earth)
ground. A closed loop ring is recommended for terminating the ground conductor
at the ground stud.
Run two wires from the circuit breaker box to a source of 48 VDC. Use appropriate
gauge wire to handle up to 60 A.
A DC-powered router that is equipped with a DC terminal block is intended only
for installation in a restricted access location. In the United States, a restricted
access area is one in accordance with Articles 110-16, 110-17, and 110-18 of
the National Electrical Code ANSI/NFPA 70.