Setting Frequency Reference Using Pulse Train Signals
When b1-01 is set to 4, the pulse train input signal at terminal RP input is used as the frequency reference.
Set H6-01 (Pulse Train Input Function Selection) to 0 (frequency reference), and then set the reference pulse
frequency that is equal to 100% of the reference value to H6-02 (Pulse Train Input Scaling).
Inverter
Pulse Input Specifications
Low level voltage
0.0 to 0.8 V
High level voltage
3.5 to 13.2 V
Pulse duty factor
30 to 70%
32 kHz max.
Pulse frequency
0 to 32 kHz
3.5 to 13.2 V
(Pulse train input terminal)
Pulse input
(Analog common)
Fig 6.9 Frequency Reference Using Pulse Train Input