Storing Inverter set values in the Digital Operator (READ)
To store Inverter set values in the Digital Operator use the following method.
Step
No.
1
Press the Menu Key and select advanced programming mode.
2
Press the DATA/ENTER Key.
Press the Increment and Decrement Key until parameter o3-01 is displayed
3
(Copy Function Selection).
4
Press the DATA/ENTER Key and select the constants setting display.
5
Change the set value to 1 using the Increment Key.
Set the changed data using the DATA/ENTER Key. The READ function will
6
start.
If the READ function ends normally, "End" is displayed on the Digital Oper-
7
ator.
8
The display returns to o3-01 when a key is pressed.
If a fault is displayed, press any key to cancel the fault display and return to the o3-01 display. Refer to
page 7-18, Digital Operator Copy Function Faults
Explanation
for corrective actions.
Digital Operator Display
-ADV-
** Main Menu **
Programming
-ADV-
Initialization
A1
- 00=1
Select Language
-ADV-
COPY Function
o3
- 01=0
Copy Funtion Sel
-ADV-
Copy Function Sel
o3-01=
0
*0*
COPY SELECT
-ADV-
Copy Function Sel
o3-01=
1
*0*
INV
OP READ
-ADV-
READ
OP READING
INV
-ADV-
READ
READ COMPLETE
-ADV-
Copy Function Sel
o3 - 01=0
*0*
COPY SELECT
6