Omron VARISPEED F7 User Manual page 91

Vector control frequency inverter
Hide thumbs Also See for VARISPEED F7:
Table of Contents

Advertisement

Parame-
Class
ter Num-
4
* The setting range is valid if Heavy Duty is selected (C6-01=0, default setting). If Normal Duty 1 or 2 is selected (C6-01=1 or 2) the setting range will be
0.0 to 400.0 Hz.
6
4-
Table 4.1 Basic Parameter Settings (Continued)
Name
ber
Input voltage set-
Sets the Inverter's nominal input voltage
E1-01
ting
in volts.
Motor rated cur-
E2-01
Sets the motor rated current.
rent
H4-02
Can be used to adjust the analog output
FM and AM ter-
and
when an instrument is connected to the
minal output gain
H4-05
FM or AM terminal.
Used to enable or disable the motor over-
load protection function.
0: Disabled
1: Protection for general purpose motor
Motor protection
L1-01
(fan cooled)
selection
2: Protection for frequency converter
motor (externally cooled)
3: Protection for special vector control
motor
If using the dynamic brake option (brak-
Stall prevention
ing resistor, Braking Resistor Units and
L3-04
selection during
Braking Units), be sure to set parameter
deceleration
L3-04 to 0 (disabled) or 3 (enabled with
braking resistor).
Description
155 to 255 V
(200 V class)
310 to 510 V
(400 V class)
10% to 200%
of Inverter's
rated current
: Must be set.
: Set as required.
Setting
Factory
Page
Range
Setting
200 V
(200 V
class)
5-31
400 V
6-113
(400 V
class)
Setting for
general-
purpose
5-32
motor of
6-51
same
6-111
capacity as
Inverter
H4-02:
0.0 to
100%
5-49
1000.0%
H4-05:
50%
5-52
0 to 3
1
6-51
5-55
0 to 3
1
6-25