Omron VARISPEED F7 User Manual page 72

Vector control frequency inverter
Hide thumbs Also See for VARISPEED F7:
Table of Contents

Advertisement

Cable Lug Connector Sizes and Tightening Torque
The lug sizes and tightening torques for various wire sizes are shown in
2
Wire Thickness [mm
]
0.5
0.75
1.25
2
Precautions
The wiring method is the same as the one used for straight solderless terminals. Refer to
the following precautions when wiring.
Separate the control signal lines for the PG Speed Control Card from main power lines and other control
circuits.
The shield must be connected to prevent operational faults caused by noise. Also, do not use any lines that
are more than 100 m long.
Connect the shield (green grounding cable of the option card) to the shield terminal (E).
Do not solder the ends of wires. Doing so may cause contact faults.
When not using straight solderless terminals, strip the wires to a length of approximately 5.5 mm
A separate power supply is required if the PG power supply consumption is higher than 200 mA. (If
momentary power loss must be handled, use a backup capacitor or other method.)
Make sure not to exceed the PG cards maximum input frequency. The output frequency of the pulse gener-
ator can be calculated using the following formula.
Motor speed at maximum output frequency (min
f
PG (Hz) =
Table 2.16 Cable Lugs and Tightening Torque
Terminal
Crimp Terminal Size
Screws
1.25 - 3.5
1.25 - 3.5
M3.5
1.25 - 3.5
2 - 3.5
60
Table
2.16.
Tightening Torque (N • m)
0.8
page
–1
)
x PG rating (p/rev)
2
2-36. Observe
37
2-

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents