Omron VARISPEED F7 User Manual page 96

Vector control frequency inverter
Hide thumbs Also See for VARISPEED F7:
Table of Contents

Advertisement

Parameter Settings for Autotuning
The following parameters must be set before autotuning.
Name
Parame-
ter Num-
Display
ber
Motor 1/2
Set the location where the auto-
selection
tuned motor data are to be stored.
*1
T1-00
1: E1 to E2 (motor 1)
Select
2: E3 to E4 (motor 2)
Motor
Autotuning
Set the autotuning mode.
mode selec-
0: Rotating autotuning
tion
T1-01
1: Non-rotating autotuning
2: Non-rotating autotuning for
Tuning
line-to-line resistance only
Mode Sel
Motor rated
power
Set the output power of the
T1-02
motor in Kilowatts.
Mtr Rated
Power
Motor rated
voltage
Set the rated voltage of the
T1-03
Rated
motor.
Voltage
Motor rated
current
Set the rated current of the motor
T1-04
in Amps.
Rated
Current
Motor rated
frequency
Set the base frequency of the
T1-05
Rated
motor.
Frequency
Number of
motor poles
T1-06
Set the number of motor poles.
Number of
poles
Motor rated
speed
Set the base speed of the motor
T1-07
in r/min.
Rated
Speed
Number of
PG pulses
Sets the number of pulses for the
per revolu-
PG (pulse generator or encoder)
T1-08
tion
per motor revolution without a
multiplication factor
PG Pulses/
Rev
* 1. Displayed only, when a motor switch command is set for a multi-function digital input (one of H1-01 to H1-05 set to 16).
* 2. Only setting 2 (non-rotating autotuning for line-to-line resistance only) is possible for V/f control or V/f control with PG.
* 3. Stable vector control will be possible when the setting is between 50% and 100%.
* 4. For an inverter motor or vector control motor, the voltage and frequency may be lower than for a general-purpose motor. Always confirm setting on the
nameplate or in test reports. Also, if you know the no-load values, set the no-load voltage in T1-03 and the no-load frequency in T1-05 to obtain better
accuracy.
* 5. The setting range is valid if Heavy Duty is selected (C6-01=0, default setting). If Normal Duty 1 or 2 is selected (C6-01=1 or 2) the setting range will be
0.0 to 400.0 Hz.
Table 4.3 Parameter Settings before Autotuning
Display
10% to 200%
of Inverter
rated output
0 to 255.0 V
(200 V class)
*4
0 to 510.0 V
(400 V class)
10% to 200%
of Inverter
current
0 to 150.0 Hz
*4
2 to 48 poles
0 to 24000
0 to 60000
Data Displays during Autotuning
Setting
Factory
Range
Setting
V/f
1 or 2
1
Yes
2 (V/f and
V/f with
Yes
PG)
0 to 2
(only
0 (Open
2)
Loop Vec-
*2
tor)
Same as
Inverter
Yes
rated out-
put
*3
200.0 V
(200 V
class)
400.0 V
(400 V
class)
Same as
general-
purpose
motor with
Yes
rated
same
*3
capacity as
Inverter
50.0 Hz
*5
4 poles
1750
r/min
1024
-
Open
Closed
V/f with
Loop
Loop
PG
Vector
Vector
Yes
Yes
Yes
Yes
(only
Yes
Yes
2)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
-
Yes
4-