Pc Switch Settings - Omron NT-series Operation Manual

Programmable terminal
Hide thumbs Also See for NT-series:
Table of Contents

Advertisement

    $    ' ( )*+*,
3-5-3

PC Switch Settings

When the NT600S and PC are connected to each other, set the conditions at the
PC CPU so as to enable the NT link communications.
The following is a general description of switch settings.

C-series C200HS, C200HX/HG/HE, CPM1, CQM1
Set the operating conditions to the PC system setting area when a C200HS or
CQM1 CPU is connected to the NT600S. The PC system setting area (data
memory) can be directly accessed from the peripheral tool (LSS etc.).
The following describes the switch settings so as to enable the PC system set-
tings. For the details of the operation with the PC system setting area, refer to the
"SYSMAC CQM1 Reference Manual" (W228-E1-
[Switch setting] (C200HS, C200HX/HG/HE, CQM1)
CPU unit DIP switch settings
[PC system setting area settings] (C200HX/HG/HE, CPM1, CQM1)
Write values to the PC system setting area (data memory) in accordance with the
CPU unit and port used for connection to the NT600S.
PC Side
RS-232 port of
C200HX/HG/HE,
DM6645
CQM1
Port A of C200HX/
DM6555
HG/HE
Port B of C200HX/
DM6550
HG/HE
CPM1
DM6650

RS-232C port communication
condition settings
Set DIP switch 5 to OFF (right side)
to enable the PC system settings.
Channel #
Writing Value
4000
Section 2-5

).
Settings
Use NT link (1:1)