Grounding - Omron NT-series Operation Manual

Programmable terminal
Hide thumbs Also See for NT-series:
Table of Contents

Advertisement

%  
Caution
3-2-3

Grounding

Note
NT600S
Class 3 grounding
(grounding resistance
is 100
or less)
Grounding for individual equipment:
Caution
Fit crimp-style terminals to the power cable. Connecting the wires of the cable to
the terminal block directly after merely twisting them together could cause fire and
other hazards.
Fork type
7 mm or less
[Recommended terminals]
Maker
Japan Solderless Terminal MFG
Fuji Terminal
Nichifu Terminal
The NT600S has a Grounding terminal
To prevent malfunctions due to excessive noise, and to prevent electric shock,
carry out class 3 grounding (grounding resistance of 100
cial-purpose grounding cable (wire of at least 2 mm
Grounding wire length should be less than 20 m.
Note that if grounding wire is used in common with other equipment, or if it is con-
nected to a beam of a building, for example, the NT600S might be adversely af-
fected by this grounding.
Other
NT600S
equipment
Correct
Grounding common to several pieces of equipment:
Carry out class 3 grounding (grounding wire must be less than 100
necting the power supply. Otherwise there will be a danger of electric shock.
Round type
7 mm or less
Type
Type
(fork type)
(round type)
2-YS3A
2-3.5
2-YAS3.5
V2-S3.5
2Y-3.5
2-3.5
.
2
).
Other
NT600S
equipment
Section 2-2
Applicable Wire
(stranded wire)
2
1.04 to 2.63 mm

or less) using a spe-
Other
equipment
Incorrect

) before con-