Installation
Note
3-1-4

Grounding

1,2,3...
Note
32
Tighten the screws on the terminal block to a torque of 0.8 N ⋅ m.
Fork type
7 mm max.
Recommended Terminals
Maker
Japan Solderless Terminal MFG
Fuji Terminal
Nichifu Terminal
Conformance to Shipbuilding Standard
• Use gaskets or other materials to completely shield all openings and
other gaps in the control panel.
• Use copper tape or other electrically conductive tape to shield gaps
between the cutout and the PT before securing the PT in place.
• To suppress noise terminal voltage, perform installation under the follow-
ing conditions. It is recommended to use the following product for the DC
power supply.
Recommended Power Supply model: S82K-03024
Manufacturer: OMRON
The NT31/NT31C has a functional ground terminal (
Carry out wiring under the following conditions.
1. In cases where there is a potential difference between the grounds of the
NT31/NT31C and the host, ground as shown in the following figure. If there
is some distance between the NT31/NT31C and host and grounding at a
single point is difficult, do not connect the functional ground terminal (
of the NT31/NT31C.
2. If the NT31/NT31C is installed in the same panel as equipment that gen-
erates noise, such as a motor or inverter, do not ground the functional
ground terminal (
NT31/
Host
NT31C
Grounding at
a single point
Carry out grounding correctly in order to prevent operating errors due to
noise.
Round type
7 mm max.
Type
(fork type)
(round type)
2-YS3A
2-3.5
2-YAS3.5
V2-S3.5
2Y-3.5
2-3.5
) of the NT31/NT31C.
Section 3-1
Type
Applicable Wire
(stranded wire)
2
2.0 to 2.63 mm
).
)