Task Debugging

4-4-4 Precautions when Debugging Task

Display Task in Program Area for Debugging
Interrupt Factor for Interrupt Task
Starting I/O Interrupt Task
No tasks other than ones used in the program area for applications are dis-
played in the [Task Control].
The interrupt factor for an interrupt task is identified by the task number if the
task is started in the [Task Control].
Interrupt factor
Power OFF interrupt task 1
Scheduled interrupt task
I/O interrupt task
External interrupt task
An I/O interrupt task will not be started even if Interrupt Input Unit is registered
in the [Register PLC Unit] window and the I/O memory area corresponding to
the input allocated to the Interrupt Input Unit is turned ON.
Task number
2,3
100 to 131
The task numbers other
than the above.
Section 4-4