I/O Memory Allocation
Address
Words
Bits
A600 to
Macro Area
A603
Input
Words
A604 to
Macro Area
A607
Output
Words
A608
A60800 Inner Board
Restart Bit
A609 to
A60900
Inner Board
A613
to
User Inter-
A61315
face Area
A619
A61901 Peripheral
Port Set-
tings
Changing
Flag
A61902 RS-232C
Port Set-
tings
Changing
Flag
A620
Communi-
cations Unit
0 Settings
Changing
Flag
A62001 Port 1
A62002 Port 2
A62003 Port 3
A62004 Port 4
Name
When MCRO(099) is executed, it
copies the input data from the
specified source words (input
parameter words) to A600
through A603 and executes the
specified subroutine with that
input data.
After the subroutine specified in
MCRO(099) has been executed,
the results of the subroutine are
transferred from A604 through
A607 to the specified destination
words.
(output parameter words).
Turn the corresponding bit ON to
restart (initialize) Inner Board 0 or
1.
The bit is turned OFF automati-
cally when the restart processing
is completed.
The data transferred from the
CPU Unit to the Inner Board is
defined and used at the Inner
Board.
The contents of these words is
retained when the power is
turned ON.
ON while the peripheral port's
communications settings are
being changed. This flag will be
turned ON when STUP(237) is
executed and it will be turned
OFF after the settings have been
changed.
ON while the RS-232C port's
communications settings are
being changed. This flag will be
turned ON when STUP(237) is
executed and it will be turned
OFF after the settings have been
changed.
The corresponding flag will be
ON when the settings for that port
are being changed.
The flag will be turned ON when
STUP(237) is executed and it will
be turned OFF by an event is-
sued from the Serial Communi-
cations Unit after the settings
have been changed.
It is also possible for the user to
indicate a change in serial port
settings by turning these flags
ON.
CS/CJ-series PLC
Function
CX-Simulator
Settings
Function
Input data:
Same as
4 words
CS/CJ-series
PLC.
Output
Same as
data:
CS/CJ-series
4 words
PLC.
---
Not used.
---
Not used.
1: Chang-
Not used.
ing
0: Not
changing
1: Chang-
Not used.
ing
0: Not
changing
1: Chang-
Not used.
ing
0: Not
changing
Section 9-3
Settings
235