Omron WS02-SIMC1-E - V1.9 REV 12-2009 Operation Manual page 262

Table of Contents

Advertisement

I/O Memory Allocation
Address
Words
Bits
A402
A40207 CS/CJ-series
CPU Bus Unit
Error Flag
(Non-fatal
error)
A40208 Inner Board
Error Flag
(Non-fatal
error)
A40209 I/O Verifica-
tion Error Flag
(Non-fatal
error)
A40210 PLC Setup
Error Flag
(Non-fatal
error)
A40212 Basic I/O Unit
Error Flag
(Non-fatal
error)
Name
ON when an error occurs in a
data exchange between the CPU
Unit and a CS/CJ-series CPU
Bus Unit (including an error in the
CS/CJ-series CPU Bus Unit it-
self).
The CPU Unit will continue oper-
ating and the ERR/ALM indicator
on the front of the CPU Unit will
flash. The CS/CJ-series CPU Bus
Unit where the error occurred will
stop operating and the unit
number of the Unit where the
data exchange error occurred is
indicated in A417.
(This flag will be turned OFF
when the error is cleared.)
ON when an error occurs in a
data exchange between the CPU
Unit and the Inner Board (in-
cluding an error in the Inner
Board itself).
The CPU Unit will continue oper-
ating and the ERR/ALM indicator
on the front of the CPU Unit will
flash. The Inner Board will stop
operating and details on the error
will be written to A424.
(This flag will be turned OFF
when the error is cleared.)
ON when a Basic I/O Unit regis-
tered in the I/O Table does not
match the Basic I/O Unit actually
installed in the PLC because a
Unit was added or removed.
ON when there is a setting error
in the PLC Setup. The CPU Unit
will continue operating and the
ERR/ALM indicator on the front of
the CPU Unit will flash.
The location of the error will be
written to A406.
(This flag will be turned OFF
when the error is cleared.)
ON when an error has occurred in
a Basic I/O Unit (including C200H
Group-2 High-density I/O Units
and C200H Interrupt Input Units).
CS/CJ-series PLC
Function
CX-Simulator
Settings
Function
1: Error in
Not used.
one or more
Units
0: No error
in any Unit
1: Error
Not used.
0: No error
1: Mis-
Not used.
match
0: No mis-
match
1: Error
Same as
0: No error
CS/CJ-
series PLC.
1: Error
Not used.
0: No error
Section 9-3
Settings
223

Advertisement