4 to 20 mA
When the resolution is set to 1/6,000, the 4- to 20-mA range corresponds to hexadecimal values
0000 to 1770 (0 to 6,000). The entire data range is FED4 to 189C (-300 to 6,300).
Inputs between 3.2 and 4 mA are expressed as two's complements. If the input falls below 3.2 mA,
open-circuit detection will activate and converted data will be 8000.

15-2-2 Analog Output Signal Ranges

-10 to 10 V Outputs
When the resolution is set to 1/6,000, the hexadecimal values F448 to 0BB8 (-3,000 to 3,000) corre-
spond to an analog voltage range of -10 to 10 V.
Specify a negative voltage as a two's complement.
F31C
8000
( 3300)
0 to 10 V Outputs
When the resolution is set to 1/6,000, the hexadecimal values 0000 to 1770 (0 to 6,000) correspond
to an analog voltage range of 0 to 10 V.
Specify a negative voltage as a two's complement.
8000
CP1E CPU Unit Software User's Manual(W480)
Converted Data
Hexadecimal (Decimal)
189C (6300)
1770 (6000)
0000 (0)
3.2 mA
0 mA
4 mA
FED4 ( 300)
11 V
10 V
F448
( 3000)
0000 (0)
0 V
0BB8
(3000)
10 V
11 V
10.5 V
10 V
FED4
( 300)
0000 (0)
0 V
1770
(6000)
0.5 V
20 mA 20.8 mA
Conversion Data
0CE4
7FFF
Hexadecimal (Decimal)
(3300)
Conversion Data
189C
7FFF
Hexadecimal (Decimal)
(6300)
15 Analog I/O Function