Analog Input And Output Signal Ranges; Analog Input Signal Ranges - Omron CP1E CPU UNIT SOFTWARE User Manual

Cp1e cpu unit software
Table of Contents

Advertisement

15-2 Analog Input and Output Signal Ranges

Analog I/O data is digitally converted according to the analog I/O signal range as shown below.
Note When the input exceeds the specified range, the AD converted data will be fixed at either the lower limit or
upper limit.

15-2-1 Analog Input Signal Ranges

-10 to 10 V Input
When the resolution is set to 1/6,000, the -10 to 10-V range corresponds to hexadecimal values
F448 to 0BB8 (-3,000 to 3,000). The entire data range is F31C to 0CE4 (-3,300 to 3,300).
A negative voltage is expressed as a two's complement.
11 V 10 V
0 to 10 V Input
When the resolution is set to 1/6,000, the 0 to 10-V range corresponds to hexadecimal values 0000
to 1770 (0 to 6,000). The entire data range is FED4 to 189C (-300 to 6,300).
A negative voltage is expressed as a two's complement.
CP1E CPU Unit Software User's Manual(W480)
Converted Data
Hexadecimal (Decimal)
0CE4 (3300)
0BB8 (3000)
0000 (0)
10 V 11 V
0 V
F448 ( 3000)
F31C ( 3300)
Converted Data
Hexadecimal (Decimal)
189C (6300)
1770 (6000)
0.5 V
0000 (0)
0 V
10 V 10.5 V
FED4 ( 300)
15 Analog I/O Function
15
15-7

Advertisement

Table of Contents
loading