13 PWM Outputs
Preparations
PLC Setup
There are no settings that need to be made in the PLC Setup.
DM Area Settings
• PWM Operand Settings (D0 and D1)
Frequency: 2,000.0 Hz
Duty factor: 40.0%
Ladder Diagram
0.00
Start input
0.01
Stop input
13-4
Setting
Operand
@PWM
PWM output 0 (Duty factor in increments of 0.1%, Frequency in increments of 0.1 Hz)
#1000
D0
Frequency setting
D1
Duty factor setting
@INI
PWM output 0
#1000
Stops pulse output
#0003
D10
Not used.
Data
D0
#4E20
D1
#0190
CP1E CPU Unit Software User's Manual(W480)