Omron CP1E CPU UNIT SOFTWARE User Manual page 362

Cp1e cpu unit software
Table of Contents

Advertisement

Appendices
Instruction
Mnemonic
ACCUMULA-
TTIM
TIVE TIMER
(BCD)
TTIMX
(Binary)
LONG TIMER
TIML
(BCD)
TIMLX
(Binary)
COUNTER
CNT
(BCD)
CNTX
(Binary)
A-8
Variations
Symbol/Operand
---
Timer
TTIM(087)
input
N
S
Reset
input
N: Timer number
S: Set value
---
Timer
TTIMX(555)
input
N
S
Reset
input
N: Timer number
S: Set value
---
TIML(542)
D1
D2
S
D1: Completion Flag
D2: PV word
S: SV word
---
TIMLX(553)
D1
D2
S
D1: Completion Flag
D2: PV word
S: SV word
---
Count
CNT
input
N
S
Reset
input
N: Counter number
S: Set value
---
Count
CNTX(546)
input
N
S
Reset
input
N: Counter number
S: Set value
Function
TTIM(087)/TTIMX(555) operates an incrementing timer with units
of 0.1-s. The setting range for the set value (SV) is 0 to 999.9 s for
TTIM(BCD) and 0 to 6,553.5 s for TTIMX(Binary).
ON
Timer input
OFF
SV
Timer PV
0
ON
Completion
Flag
OFF
ON
Reset input
OFF
TIML(542)/TIMLX(553) operates a decrementing timer with units
of 0.1-s that can time up to approx. 115 days for TIML(BCD) and
49,710 days for TIMLX(Binary).
ON
Timer input
OFF
SV
Timer PV
0
Completion Flag
ON
(Bit 00 of D1)
OFF
CNT/CNTX(546) operates a decrementing counter. The setting
range for the set value (SV) is 0 to 9,999 for CNT(BCD) and 0 to
65,535 for CNTX(Binary).
ON
Count input
OFF
ON
Reset input
OFF
SV
Counter PV
0
ON
Completion
Flag
OFF
CP1E CPU Unit Software User's Manual(W480)
Timing
resumes.
PV
maintained.