Error Status - Omron CP1E CPU UNIT SOFTWARE User Manual

Cp1e cpu unit software
Table of Contents

Advertisement

Error Status

The status of errors that occur at the Ethernet Option Board is reflected as shown in the following dia-
gram.
15 14 13 12 11 10
CIO 81
Bit
Name
0 to 1
Reserved
2
IP address setting
error
3
IP address table
error
4
IP router table error
5 to 6
Reserved
7 to 12
Reserved
13
Baud rate disagree-
ment
14
Address disagree-
ment
15
EEPROM error
FINS/TCP Connection Status
15 14 13 12 11 10
CIO 81
0
0
Bit
0
FINS/TCP Connection No.1
1
FINS/TCP Connection No.2
2 to 15
Reserved
CP1E CPU Unit Software User's Manual(W480)
9
8
7
0
0
0
0
0
0
Band rate disagreement
Address disagreement
EEPROM error
Always 0.
The following cannot be used as IP address set-
tings.
• Host IDs that are all 0 or all 1.
• Network IDs that are all 0 or all 1.
• Subnetwork IDs that are all 1.
• Addresses beginning with 127 (7F hex).
Reset the IP address.
Correct the IP address table. If the problem cannot be
resolved, replace the CPU Unit.
Correct the IP router table. If the problem cannot be
resolved, replace the CPU Unit.
Always 0.
Always 0.
Make sure that the baud rate setting of the Serial
Option Port is 115,200 bps. Change the baud rate of
the Serial Option Port.
Make sure that the node number and the last byte of
the IP address are the same and then set other host
IDs to 0. Change the address conversion method.
Restart the PC. If the problem cannot be resolved,
replace the Ethernet Option Board.
9
8
7
0
0
0
0
0
0
0
Switch
0: The connection is terminated.
1: A connection is established.
0: The connection is terminated.
1: A connection is established.
Always 0.
6
5
4
3
2
1
0
0
0
0
0
IP address setting error
IP address table error
IP router table error
Correction
6
5
4
3
2
1
0
0
0
0
0
0
Unit operation
17 Ethernet Option Board
17
17-31