Built-In Inputs; High-Speed Counter Settings - Omron CP1E CPU UNIT SOFTWARE User Manual

Cp1e cpu unit software
Table of Contents

Advertisement

7-2-6

Built-in Inputs

High-speed Counter Settings

1
Use high-speed counter 0
1-1
Counting mode
1-1-1
1-2
Reset
Note Only a software reset can be
set if an increment pulse
input is set for the input set-
ting.
1-3
Input Setting
Note Make the same input setting
for high-speed counters 0, 1,
and 2.
2
Use high-speed counter 1
2-1
Counting mode
2-1-1
2-2
Reset
Note Only a software reset can be
set if an increment pulse
input is set for the input set-
ting.
2-3
Input Setting
Note Make the same input setting
for high-speed counters 0, 1,
and 2.
3
Use high-speed counter 2
3-1
Counting mode
3-1-1
3-2
Reset
3-3
Input Setting
CP1E CPU Unit Software User's Manual(W480)
Name
Do not use.
Linear mode
Circular Max. Count
0
Z phase, software reset
(stop comparing)
Differential phase input
(×4)
Do not use.
Linear mode
Circular Max. Count
0
Z phase, software reset
(stop comparing)
Differential phase input
(×4)
Do not use.
Linear mode
Circular Max. Count
0
Software reset
Increment pulse input
Default
Possible settings
Do not use.
Use.
Linear mode
Circular mode
0
:
4,294,967,295
Z phase, software reset (stop
comparing)
Software reset
(stop comparing)
Phase Z, software reset (compar-
ing)
Software reset (comparing)
Differential phase input (×4)
Pulse + direction input
Up/Down pulse input
Increment pulse input
Do not use.
Use.
Linear mode
Circular mode
0
:
4,294,967,295
Z phase, software reset (stop
comparing)
Software reset
(stop comparing)
Phase Z, software reset (compar-
ing)
Software reset (comparing)
Differential phase input (×4)
Pulse + direction input
Up/Down pulse input
Increment Pulse input
Do not use.
Use.
Linear mode
Circular mode
0
:
4,294,967,295
Software reset
Software reset (comparing)
Increment pulse input
7 PLC Setup
When setting is read by
CPU Unit
When power is turned ON
At start of operation
At start of operation
When power is turned ON
When power is turned ON
When power is turned ON
At start of operation
At start of operation
When power is turned ON
When power is turned ON
When power is turned ON
At start of operation
At start of operation
When power is turned ON
When power is turned ON
7-11