9-1-2
Flow of Operation
1
2
Create ladder
program
Precautions for Correct Use
Precautions for Correct Use
A built-in input cannot be used as a quick-response input if it is being used as a normal input,
interrupt input, or high-speed counter input. Refer to 8-3-3 Allocating Built-in Input Terminals for
details.
PLC Setup
Click the Built-in Input Tab and select Quick in the interrupt input settings.
Select Quick
Built-in Input Tab Page
Quick-response input setting
IN2
Select Quick for IN2
to IN7.
IN3
IN4
IN5
IN6
IN7
Note 1 The power supply must be restarted after the PLC Setup is transferred in order to validate the quick-
response input settings.
2 IN6 and IN7 are not supported by E10 CPU Units.
CP1E CPU Unit Software User's Manual(W480)
• Set IN2 to IN7 for quick-response inputs on the Built-in Input
PLC Setup
• The terminals 02 to 07 of CIO 0 can be used for quick-
Read the status of CIO 0.02 to CIO 0.07 using the LD instruction
Cyclic task or
or other instructions.
interrupt task
Corresponding bit address
CIO 0.02
CIO 0.03
CIO 0.04
CIO 0.05
CIO 0.06
CIO 0.07
9 Quick-response Inputs
Tab Page of the PLC Setup using the CX-Programmer.
response inputs. Bits CIO 0.02 to CIO 0.07 correspond to ter-
minals 02 to 07.
9
9-3