Chapter 3
Driving inverter requires a frequency reference and an operation command.
Set "Run command source" and "Frequency reference source" referring to this chapter.
(For more details,Please contact your supplier or local Hitachi inverter sales office.)
◼ Frequency source 1

3.3 Frequency setting from keypad

Select [AA101] = 07 :Parameter Setting.
(Frequency reference is selected by parameter setting.)
Changing frequency setting from each source
(1) [FA-01] "Main speed reference setting or monitor" or
(2) [Ab110] "Multi-speed 0 setting, 1st-motor"
Eg.) For [FA-01]
−
◼ Frequency source
・Use the up, down, left and right arrow keys to change
the frequency reference setting by [FA-01] "Main speed
reference setting or monitor" or [Ab110] "Multi speed
0 setting, 1st motor".
◼ Parameter
Parameter
Main speed input source
[AA101]
selection, 1st-motor
Main speed reference
[FA-01]*)
setting or monitor
Multi-speed 0 setting,
[Ab110]*)
1st-motor
*) While [AA101] = 07, a change made in either [FA-01]
or [Ab110] will be automatically reflected in the
other. When no change can be made or is reflected
in [FA-01], the operator keypad is not specified as a
command source by the terminal function or
[AA101].
・The frequency setting value should be set to other
than 0.00.
・When the main speed command can be set on the
keypad, the output terminal 010[FREF]turns ON.
Setting
Details
data
07
0.00Hz
0.00Hz
Operation Setting and Examples of I/O Adjustment
◼ Run command source 1

3.4 Run key using on the keypad

Select [AA111] = 02 : keypad's RUN-key.

◼ Run/stop command
Press the RUN key and STOP key on the operator
keypad to start and stop the inverter, respectively.
◼ Parameter
Parameter
[AA111]
・When the RUN command can be input from the
keypad, the output terminal [REF]"Run
command=Keypad" turns ON.
・In addition, when the RUN command is input, not
limited to the RUN key on the keypad, the output
terminal 031[FR] starting contact signal turns ON.
3-2
Details
Setting data
Run command input
source selection,
1st-motor.
02