Installation and mounting
5.5 Installing the dispenser
5.5.2

Removing the cable gland plate

Removing the cable gland plate
Remove the cable gland plate before positioning the dispenser. To do this, proceed as
follows:
1. Open the device door.
2. Remove the four screws of the cable gland plate.
3. Remove the cable gland plate.
Figure 5-7  Cable gland plate
5.5.3

Positioning the dispenser and inserting the cables

To install the dispenser at the site, you must lift the dispenser from the load carrier with a
crane (see Section 4 "Transport and storage" (Page 29)). Then transport the dispenser to the
prepared base area. We recommend using a crane for lifting and positioning.
Lifting the dispenser from the load carrier
Suspended load
Falling of the dispenser or any of its parts may result in death or serious injury. Stay
completely away from any hazardous areas.
1. Open the device door.
2. Remove the cable gland plate and close the door.
3. Attach the crane lugs to the 4 corners of the cabinet frame to the roof.
If you use own crane lugs, they have to fulfill the following requirements:
– 25 to 30 mm long M12 thread
– Pay attention to the weight of the dispenser.