Installation and mounting

5.2 Installation location

• Installation tester
• Ethernet cable with RJ45 connector
See also
Installation and commissioning video
siemens.highspot.com/items/614c6e89917589fd3aa36656?lfrm=rhp.25)
5.2
Installation location
For safe operation of the dispenser, you need a location that meets the following
requirements.
Selection criteria for a safe location
Select the location in such a way that all operations can be carried out safely. The dispenser
itself must not pose a hazard to persons or vehicles.
NOTE
Do not install the dispenser in an open area
Do not install the dispenser in an open area without an interception rod or external lightning
protection. Otherwise, complete protection cannot be guaranteed.
Noise emission
Select the location of the dispenser so that the specifications of the Technical Instructions for
Protection Against Noise (TA Noise)
z/fachbegriffe-s-u/ta-laerm-fachbegriff/) are adhered to. You can find more information in
section Declaration of Conformity (Page 80).
Minimum clearances
To enable operation and service and to ensure proper ventilation of the dispenser, you must
maintain the following minimum clearances:
Figure 5-1  Minimum clearances of SICHARGE D dispenser, top view
38
(https://see-
(https://www.bfga.de/arbeitsschutz-lexikon-von-a-bis-
Operating Instructions, 10/2023, A5E52758387-AB