6.4

Restarting the charging station

You can restart the charging station either on site or via remote access from the SICHARGE
Configuration Backend SCB. When a door is opened, 2 further buttons appear on the
SICHARGE D display next to the notice about the door. The charging station is shut down with
"Restart" and restarts again after a short wait time.
6.5

Service mode

You can activate the service mode via the SICHARGE Configuration Backend SCB. Active
charging processes are not terminated. When no more charging processes are active, the
circuit breaker disconnects the power trains for charging from the power supply system. The
controller and the display remain powered in this state. Then, the service personnel on
location can open the door of the charging station.
Electric shock due to residual charges in capacitors
The discharging process of the capacitors starts after the charging station power supply has
been switched off. Live parts remain under dangerous electrical voltage for up to 10 minutes
during discharging. Touching the live parts can lead to death or serious injury.
• Wait approximately 10 minutes after switching off the power supply.
• Make sure that the charging station is de-energized.
• Only then is it safe to start work on the charging station.
Hot surfaces
When opening the front or back door, you can easily come into contact with hot surfaces.
This applies, for example, to the area of the AC/DC converters or the copper bars. Before
starting work, wait at least 10 minutes after switching off the charging station until all hot
surfaces have cooled down.
You can change different configurations of the controller in service mode. For example, it is
possible to change the limiting of power drawn from the grid and the power of the DC
charging points.
Lock the doors when you have finished the work. Exit service mode afterwards via the SCB by
accepting or rejecting your changes. The circuit breaker then reconnects. The charging
station begins restoring charging readiness.
If you need to disconnect the charging station from the power supply for further work, open
a door and confirm the shutdown via the button on the display. As soon as the display has
switched off, the upstream switching device must be used to isolate the charging station.
Always follow the five safety rules for electrical work.