If optimal conditions cannot be provided with a dedicated panel, the use of an
Isolation Transformer with the following characteristics it is recommended:
120/208/240 V input, over-current protected at primary
120/208/240 V available at secondary outputs, each
circuit breaker-protected
Primary and secondary windings must be fully isolated from one another
Certified for use locally as a stand alone user product (CSA, UL, or other
locally recognized markings apparent)
Capable of providing power to all Option 11C system equipment
operating simultaneously at full load
Equipment unrelated to the Option 11C system must not be powered
from a transformer serving the Option 11C system.
,VRODWLRQ#WUDQVIRUPHU#JURXQG
It is recommended that the transformer ground have the following
characteristics:
Separate grounds for primary and secondary windings rather than
common ground
A "clean" and permanent SPG reference at the transformer secondary for
the Option 11C system.
In addition, verify the ground conductors inside the transformer to ensure
they are sized appropriately.
Note: Do not ground the transformer or Option 11C system to structural
steel or water pipes. Connect them to a known building ground reference.