If optimal conditions cannot be provided with a dedicated panel, the use of an
Isolation Transformer with the following characteristics it is recommended:
•
120/208/240 V input, over-current protected at primary
•
120/208/240 V available at secondary outputs, each
circuit breaker-protected
•
Primary and secondary windings must be fully isolated from one another
•
Certified for use locally as a stand alone user product (CSA, UL, or other
locally recognized markings apparent)
•
Capable of providing power to all Option 11C system equipment
operating simultaneously at full load
•
Equipment unrelated to the Option 11C system must not be powered
from a transformer serving the Option 11C system.
,VRODWLRQ#WUDQVIRUPHU#JURXQG
It is recommended that the transformer ground have the following
characteristics:
•
Separate grounds for primary and secondary windings rather than
common ground
•
A "clean" and permanent SPG reference at the transformer secondary for
the Option 11C system.
In addition, verify the ground conductors inside the transformer to ensure
they are sized appropriately.
Note: Do not ground the transformer or Option 11C system to structural
steel or water pipes. Connect them to a known building ground reference.