Nortel Meridian 1 option 11C Planning And Installation Manual page 179

Hide thumbs Also See for Meridian 1 option 11C:
Table of Contents

Advertisement

&KDSWHU#49#±#,QVWDOOLQJ#DQG#FRQQHFWLQJ#
UHVHUYH#SRZHU#VXSSOLHV
*HQHUDO#LQIRUPDWLRQ
7\SHV#RI#UHVHUYH#SRZHU
This chapter describes how to install and connect a reserve DC power supply
to Option 11C cabinets.
If installing a multiple-cabinet system, each cabinet must have its own reserve
power supply.
The types of reserve battery power are:
The NTAK75 battery box, which has the following features:
— designed to be float-charged by the NTDK78 ac/dc power supply
— provides a minimum of 2 hours of reserve DC power
— mounts to the floor
— supports one system cabinet
The NTAK76 battery box, which has the following features:
— designed to be float-charged by the NTDK78 ac/dc power supply
— provides a minimum of 15 minutes of reserve DC power
— mounts to the wall
— supports one system cabinet