Nortel Meridian 1 option 11C Planning And Installation Manual page 40

Hide thumbs Also See for Meridian 1 option 11C:
Table of Contents

Advertisement

3DJH#73#RI#699
#&KDSWHU#6#²#6\VWHP#DQG#VLWH#UHTXLUHPHQWV
*URXQGLQJ#UHTXLUHPHQWV
886063540543
6WDQGDUG#8133
Before installing an Option 11C and applying AC power, measure the
impedance of the building ground reference. (An ECOS 1023
POW-R-MATE or similar meter is suitable for this purpose.) If the ground
path connected to the Option 11C has an impedance of 5 Ohms or more, better
grounding arrangements should be made. Any improvements to the
grounding system should be made before the Option 11C is installed.
Other grounding requirements are as follows:
The impedance of the link between the ground post of the system
cabinets and the Single Point Ground (SPG) to which it is connected
must be less than 0.25 Ohms.
Never connect the single point ground conductor from the Option 11C
system to structural steel members or electrical conduit. In particular,
never tie this conductor to a ground source or grounded electrode that is
not hard-wired to the building reference conductor.
Ground conductors for the Option 11C system:
— must not be smaller than #6 AWG (#40 metric) at any point
— must be routed through the same conduit as the phase conductors
serving the system
— must not be smaller than any phase conductor in the same conduit
— do not carry current under normal operating circumstances.
All ground conductors in the building:
— must be isolated from the neutral bus except at the service entrance
to the building
— must be hardwired to the main ground reference.
Avoid spliced conductors. Continuous conductors have lower impedance
and are more reliable than spliced ones.
$SULO#5333

Advertisement

Table of Contents
loading

Table of Contents