Reference Limits
D2 – 01
Reference Upper Limit
Sets the maximum reference as a percent of maximum speed, E7-06.
Minimum Maximum Description
000.0
110.0
D2 – 02
Reference Lower Limit
Sets the minimum reference as a percent of maximum speed as entered in E1-06.
Minimum Maximum Description
000.0
100.0
PG Option Set-up
F1 – 02
Disconnection Detection Stopping Method
Selects the stopping method when a disconnected PG is detected.
Setting
F1 – 03
Overspeed Detection Stopping Method
Selects the stopping method when an overspeed condition is detected.
Setting
F1 – 04
Deviation Detection Stopping Method
Selects the stopping method when excessive speed deviation is detected.
Setting
50
Speed Reference Upper Limit
Speed Reference Upper Limit
Description
0
Ramp to stop - according to C1-02. (Declaration time 1)
1
Coast to stop (factory default).
2
Fast - stop - according to C1-09.
3
Alarm flashes, operation continues.
Description
0
Ramp to stop - according to C1-02 (Declaration time 1).
1
Coast to stop (factory default).
2
Fast-stop - according to C1-09.
3
Alarm flashes, operation continues. (
Description
0
Ramp to stop - according to C1-02 (Declaration time 1).
1
Coast to stop.
2
Fast-stop - according to C1-09.
3
Alarm flashes, operation continues (factory default).
Default Setting
Default Setting