YASKAWA VS-616PS5 Series Quick Start Manual page 69

Brushless motor drive
Hide thumbs Also See for VS-616PS5 Series:
Table of Contents

Advertisement

Fault Display
Multi-function analog
input selection fault
OPE07
(OPE07)
Multi-function input/
OPE08
output selection fault
(OPE08)
R/min setting fault
OPE0 10
(OPE10)
Energy-saving control
OPE0 12
constants setting fault
Digital operator fault
OPR
(OPr)
ERR
EEPROM writing fault
EEPROM R/W
(ERR)
Err
Control circuit fault 1
CPF00
(CPF00)
COM-ERR
Digital operator trans-
(OP&INV)
mission fault
Control circuit fault 2
CPF01
(CPF01)
COM-ERR
Digital operator trans-
(OP&INV)
mission fault
CPF02
Base block circuit fault
(CPF02)
BB Circuit Err
CPF03
EEPROM fault
(CPF03)
EEPROM Error
CPF04
CPU internal A/D con-
verter fault (CPF04)
Internal A/D Err
CPF05
CPU external A/D con-
verter fault (CPF05)
External A/D Err
68
Name
C-option is A1-14B and option/inverter
change is selected.
Any of the following setting faults has
occurred:
• The setting unused in the control method is
selected for F4-01 and F4-04.
• The setting unused in the control method is
selected for F5-01 and F4-02.
• The setting unused in the control method is
selected for H1-01 and H1-06.
• The setting unused in the control method is
selected for H2-01 and H2-03.
• The setting unused in the control method is
selected for H3-05 and H3-09.
• The setting unused in the control method is
selected for H4-01 and H4-04.
• The setting unused in the control method is
selected for o1-01.
The settings of E1-06 to E1-08 do not satisfy
the following conditions:
E1-06
Energy-saving control constant values are out
of range.
The digital operator was disconnected during
operation by run command from the digital
operator.
EEPROM internal data did not match when
initializing the parameter.
Transmission between the inverter and digital
operator cannot be established 5 seconds
after supplying power.
MPU peripheral element check fault (on-line)
Transmission between the inverter and digital
operator is established once after supplying
power, but later transmission is interrupted for
more than 2 seconds.
MPU peripheral element check fault (on-line).
Inverter PCB control board fault.
Description
E1-07
E1-08
Corrective Action
Check and set the constant
data.
Check and set the constant
data.
Check and set the constant
data.
Check and set the constant
data.
• Check the wiring cable and the
digital operator connection.
• Replace the control card.
Replace the control board.
Insert the operator connector
again.
Check the wiring of control cir-
cuit.
Replace the control board.
Insert the digital operator con-
nector again.
Check the digital control circuit
wiring.
Replace the control board.
Replace the control board.
VS-616PS5 Installation & Quick Start Manual