3 Part Names and Basic Procedures
3-3-3

Setting Levels

On the E5@C, the parameters are classified into levels according to their applications. These levels are
called setting levels. The setting levels consist of some basic setting levels and other setting levels.
Moving between Setting Levels
The following figure gives an overall image of the setting levels. The setting levels consist of the basic
setting levels (shaded below) and the other setting levels (not shaded).
The Initial Setting Level, Communications Setting Level, Advanced Function Setting Level, and Calibra-
tion Level can be used only when control is stopped. If you change to any of these levels, control will
stop.
Manual Control
Level
Used to set the MV
manually.
Set the Auto/Manual Select Addition parameter to ON and set the PF Setting parameter to a-m
*1
(Auto/Manual).
*2
The No. 1 display will flash when the keys are pressed for 1 s or longer.
Set the PF Setting parameter to pfdp (monitor/setting items).
*3
3 - 10
Only when Manual Mode was
used just before power OFF
Power ON
Level changes
Press O Key for at least 1 s
automatically.
*1
or S Key for at least 1 s
Operation Level
Used for SP, alarm
values, and other basic
O Key for
Press
settings and monitoring.
at least 3 s while
a-m is
*2
displayed.
*1
S Key for at least 1 s
Press O Key for
*2
at least 3 s
Initial Setting Level
Used to set the input
type and other basic
settings.
Release protection and then
enter the password (−169)
for the amoV (Move to
Advanced Function Setting
Advanced Function
Level) parameter.
Setting Level
Advanced settings
Enter the password (1201) for
the Move to Calibration Level
parameter.
Calibration Level
Press O + M Keys
for at least 1 s
Used to set protection
for operations.
Press the O Key once.
Adjustment Level
Used to change
adjustment parameters
(PID constants, control
hysteresis, etc.).
*3
Press S Key.
Press O Key for
at least 1 s
Monitor/Setting
Press O Key for
Item Level
at least 3 s
Used to display
specified monitor
and setting items.
Press O Key once
(models with communications only).
O Key for at least 1 s
000
E5@C Digital Temperature Controllers User's Manual (H174)
Protect Level
Press O + M Keys
*2
for at least 3 s.
*3
Press S Key.
Press O + M Keys
*2
for at least 3 s.
000
Communications
Setting Level
Communications settings