5-23 Initializing Settings

You can set the Parameter Initialization parameter (Advanced Function Setting Level) to fact (initialize
parameters to defaults given in the manual) to return all of the parameter settings to the factory
defaults.
The default is OFF.
Operating Procedure
Moving to the Advanced Function Setting Level
*
Refer to 4-1-4 Moving to the Advanced Function Setting Level for the procedure to enter the Advanced
Function Setting Level if you have not done so before.
1
Press the O Key for at least 3 seconds in the Operation Level.
The No. 1 display will flash when the key is pressed for 1 s or
longer.
The display will change from the Operation Level to the Initial
Setting Level.
2
Press the M Key several times in the Initial Setting Level to
display the Move to Advanced Function Setting Level parame-
ter.
amov (Move to Advanced Function Setting Level) will be displayed.
3
Press the U and D Keys at the Move to Advanced Function
Setting Level parameter and then enter -169.
You can hold the U or D Key to increment or decrement the set value
*
quickly.
4
Press M Key once or wait for 2 seconds or longer without
doing anything. You will move to the Advanced Function Set-
ting Level and init (Parameter Initialization) will be displayed.
Parameter Initialization
1
Display the first parameter, init (Parameter Initialization) in
the Advanced Function Setting Level.
2
Press the U or D Key to select fact (initialize to the factory
settings described in the manual). The parameter settings will
be initialized.
The default is off.
*
The parameter mask settings are not initialized when other settings are initialized.
Refer to Parameter Mask Enable on page 6-6.
E5@C Digital Temperature Controllers User's Manual (H174)
5 Advanced Operations
Operation Level
25
0
Initial Setting Level
in-t
Input Type
5
Initial Setting Level
Move to
amov
Advanced
Function
0
Setting Level
Move to Advanced
amov
Function Setting
Level
-169
−169: Password
to move to
Advanced
Function Setting
Level
Advanced Function Setting
Level
init
Parameter
Initialization
off
init
fact
5 - 75