Precautions When Wiring - Omron E5GC User Manual

Digital temperature controllers
Hide thumbs Also See for E5GC:
Table of Contents

Advertisement

2 Preparations
2-2-8

Precautions when Wiring

• Separate input leads and power lines in order to prevent external noise.
• Use crimp terminals when wiring the screw terminals.
• Use the suitable wiring material and crimp tools for crimp terminals.
• Tighten the terminal screws to a torque of 0.43 to 0.58 N·m. The specified torque is 0.5 N·m for the
E5CC-U.
E5CC, E5EC, E5AC, E5DC, and E5GC (Models with Screw Terminal Blocks)
and E5CC-U (Plug-in Models)
Wires
Use the wire specifications given in the following table.
Model
E5CC, E5EC, E5AC,
E5DC, and E5GC
E5CC-U
Crimp Terminals
For the E5CC, E5EC, E5AC, E5DC, or E5GC, use the following types of crimp terminals for M3 screws.
For the E5CC-U, use the following types of crimp terminals for M3.5 screws.
• If you use crimp terminals for the E5DC, use crimp terminals with insulation sleeves. If you use a bare
crimp terminal with no insulation, the terminal may short with the terminal above or below it. If you
use bare crimp terminals, cover the crimped sections with insulating marking tubes. Secure the
marking tubes so that they do not move.
Although you can connect two crimp terminals with insulation sleeves to one terminal, you cannot do
so if the diameter of the insulation sleeves is too large.
Recommended Crimp Terminals with Insulation Sleeves for the E5DC
Manufacturer
J.S.T. Mfg. Co.
2 - 44
Recommended wires
AWG24 to AWG18 ( 0.21 to 0.82 mm
AWG24 to AWG14 ( 0.21 to 2.08 mm
5.8 mm max.
5.8 mm max.
7.2 mm max
7.2 mm max
NA
OK
Model number
V1.25-B3A
V0.5-3A
Stripping length
2
6 to 8 mm (when crimp terminals are not
)
used)
2
5 to 6 mm (when crimp terminals are not
)
used)
E5@C Digital Temperature Controllers User's Manual (H174)