Omron E5GC User Manual page 319

Digital temperature controllers
Hide thumbs Also See for E5GC:
Table of Contents

Advertisement

at-g
at-h
lcma
• Normally use the default values for these parameters.
• The AT Calculated Gain parameter sets the gain for when PID values are calculated using
AT. When emphasizing response, decrease the set value. When emphasizing stability,
Function
increase the set value.
• The AT Hysteresis parameter sets the hysteresis for limit cycle operation during
autotuning when switching ON and OFF.
• The Limit Cycle MV Amplitude parameter sets the MV amplitude for limit cycle operation
during autotuning.
AT Calculated Gain
Setting
AT Hysteresis
Limit Cycle MV Amplitude 5.0 to 50.0
Related Parameters
See
See
AT Execute/Cancel (Adjustment Level): Page 6-20
inf
• This parameter sets the time constant for the input digital filter. The following diagram
shows the effect on data after passing through the digital filter:
Function
A
Setting
E5@C Digital Temperature Controllers User's Manual (H174)
000
AT Calculated Gain
000
AT Hysteresis
Limit Cycle MV Amplitude
Parameter name
Setting range
0.1 to 10.0
Temperature
input: 0.1 to 999.9
Analog input:
0.01 to 9.99
Input Digital Filter
PV before passing through filter
PV after passing through filter
0.63 A
(Time constant)
Input digital filter
Setting range
0.0 to 999.9
Control must be set to 2-PID control.
Control must be set to 2-PID control or close
000
position-proportional control.
Unit
---
Position-proportional Model: 1.0
°C
°F
%FS
%
Time
Unit
Default
Seconds
0.0
6 Parameters
Default
Standard Model: 0.8
0.8
1.4
0.20
20.0
6 - 67
6

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5ccE5ecE5acE5dcE5 c seriesE5cc-u ... Show all

Table of Contents