Omron E5GC User Manual page 303

Digital temperature controllers
Hide thumbs Also See for E5GC:
Table of Contents

Advertisement

alh1
alh2
alh3
alh4
• These parameters set the hysteresis for alarms 1, 2, 3, and 4.
Function
Alarms Other Than an MV Alarm
Setting
Temperature input
MV Alarms
Related Parameters
See
See
Alarm Value 1 to 4 (Operation Level): Page 6-14
Alarm Value Upper Limit 1 to 4 and Alarm Value Lower Limit 1 to 4 (Operation Level):
Page 6-15
Alarm 1 to 4 Type (Initial Setting Level): Page 6-47
Standby Sequence Reset (Advanced Function Setting Level): Page 6-63
Auxiliary Output 1 to 4 Open in Alarm (Advanced Function Setting Level): Page 6-64
Alarm 1 to 4 Latch (Advanced Function Setting Level): Page 6-70
E5@C Digital Temperature Controllers User's Manual (H174)
Alarm 1 Hysteresis
Alarm 2 Hysteresis
Alarm 3 Hysteresis
Alarm 4 Hysteresis
Setting range
0.1 to 999.9
Analog input
0.01 to 99.99
Setting range
0.01 to 99.99
Alarm 1 must be assigned.
The alarm 1 type must not be 0, 12, or 13.
Alarm 2 must be assigned.
The alarm 2 type must not be 0, 12, or 13.
Alarm 3 must be assigned.
The alarm 3 type must not be 0, 12, or 13.
Alarm 4 must be assigned.
The alarm 4 type must not be 0, 12, or 13.
Unit
Default
°C or °F
0.2
%FS
0.02
Unit
Unit
%
0.50
6 Parameters
6
6 - 51

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5ccE5ecE5acE5dcE5 c seriesE5cc-u ... Show all

Table of Contents