6 Parameters
amad
• This parameter sets whether the Auto/Manual Select Addition parameter is to be
displayed.
Function
Setting
Related Parameters
See
See
Auto/Manual Switch (Operation Level): Page 6-9
mant
If this parameter is set to HOLD when control moves from Automatic Mode to Manual Mode,
the final MV from Automatic Mode will be used as the initial manual MV. If this parameter is
set to INT, the setting of the Manual MV Initial Value parameter will be used as the initial
Function
manual MV.
Setting
Related Parameters
See
See
Manual MV Initial Value (Advanced Function Setting Level): 6-75
6 - 74
Auto/Manual Select Addition
Setting range
on: Displayed, off: Not displayed
Manual Output Method
Setting range
hold: HOLD, init: INIT
Control must be set to 2-PID control.
Default
Standard Model: off
Position-proportional Model: on
Control must be set to 2-PID control.
A Position-proportional Model set to Close Control
with the Direct Setting of Position-proportional MV
parameter set to ON must be used.
Default
hold
E5@C Digital Temperature Controllers User's Manual (H174)