A Appendices
A-1-2
Characteristics
Thermocouple
Indication
accuracy
(when mounted
Resistance
individually,
thermometer
ambient
Analog input
temperature of
CT input
23°C)
Potentiometer
input
Temperature
variation influence
Thermocouple
*2
Voltage variation
*2
influence
Resistance
Electromagnetic
thermometer
interference
Analog input
influence
(according to EN
CT input
61326-1)
Remote SP input
Installation
influence (E5DC
Thermocouple
only)
Temperature input
Hysteresis
Analog input
Temperature input
Proportional
band (P)
Analog input
*
3
Integral time (I)
*
3
Derivative time (D)
Control Period
Manual reset value
Alarm setting range
Sampling cycle
Insulation resistance
Dielectric strength
Malfunction vibration
Vibration resistance
Malfunction shock
A - 4
E5CC, E5CC-B, E5EC, E5EC-B, E5AC, E5DC, and E5GC:
(±0.3% of indication value or ±1°C, whichever is greater) ±1 digit max.
*
1
E5CC-U:
(±1% of PV or ±2°C, whichever is greater) ±1 digit max.
(±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max.
±0.2% FS ±1 digit max.
±5% FS ±1 digit max.
±5% FS ±1 digit max.
Thermocouple (R, S, B, W, PLII)
(±1% of indication value or ±10°C, whichever is greater) ±1 digit max.
Other thermocouples:
(±1% of indication value or ±4°C, whichever is greater) ±1 digit max.
*K thermocouple at −100°C max: ±10°C max.
(±1% of indication value or ±2°C, whichever is greater) ±1 digit max.
±1% FS ±1 digit max.
±5% FS ±1 digit max.
±1% FS ±1 digit max.
R, S, B, W, or PLII thermocouple: (±1% of indication value or ±10°C, whichever
is greater) ±1 digit max.
Other thermocouple: (±1% of indication value or ±4°C, whichever is greater) ±1
digit max.
K thermocouple at −100°C max: ±10°C max.
*
0.1 to 999.9°C or °F (in units of 0.1°C or °F)
0.01% to 99.99% FS (in units of 0.01% FS)
0.1 to 999.9°C or °F (in units of 0.1°C or °F)
0.1% to 999.9% FS (in units of 0.1% FS)
Standard, heating/cooling, or close position-proportional control: 0 to 9,999 s
(in 1-s increments) or 0.0 to 999.9 s (in 0.1-s increments)
Floating position-proportional control: 1 to 9,999 s (in 1-s increments) or 0.1 to
999.9 s (in 0.1-s increments)
0 to 9,999 s (in units of 1 s)
0.0 to 999.9 s (in units of 0.1 s)
0.1, 0.2, 0.5, or 1 to 99 s (in units of 1 s)
0.0% to 100.0% (in units of 0.1%)
−1,999 to 9,999 (except for MV alarm)
Temperature input: The decimal point is automatically set when the sensor
is selected.
Analog input: The decimal point depends on the Decimal Point parameter
setting.
−199.9 to 999.9 (MV alarm)
50 ms
20 MΩ min. (at 500 VDC)
100 to 240 VAC: 3,000 VAC, 50/60 Hz for 1 min between terminals of different
charge
24 VAC/DC: 3,000 VAC,* 50/60 Hz for 1 min between terminals of different
charge
*E5GC only: 2,300 VAC
2
10 to 55 Hz, 20 m/s
for 10 min each in X, Y and Z directions
2
10 to 55 Hz, 20 m/s
for 2 hr each in X, Y, and Z directions
2
100 m/s
, 3 times each in X, Y, and Z directions
E5@C Digital Temperature Controllers User's Manual (H174)