5 Advanced Operations
Setting Example to Output 1 to 5 V for the Process Value (−50 to 200°C,
Input Type 5)
Operating Procedure
• Setting the Transfer Output Signal Type
1
Press the M Key several times in the Initial Setting Level to
display trst (Transfer Output Signal Type).
2
Press the U or D to select 1-sv (1 to 5 V).
The default is 4-20.
• Setting the Transfer Output Type
1
Press the M Key several times in the Initial Setting Level to
display tr-t (Transfer Output Type).
2
Press the U or D Key to select pv (Process Value).
The default is off.
• Setting the Transfer Output Upper Limit
1
Press the M Key several times in the Initial Setting Level to
display tr-h (Transfer Output Upper Limit).
2
Press the U or D Key to set the value to 200.
The default is 1300.
• Setting the Transfer Output Lower Limit
1
Press the M Key several times in the Initial Setting Level to
display tr-l (Transfer Output Lower Limit).
2
Press the U or D Key to set the value to −50.
The default is −200.
5 - 38
Initial Setting Level
trst
off
trst
1-sv
Initial Setting Level
tr-t
off
tr-t
Initial Setting Level
tr-h
1300
tr-h
200
Initial Setting Level
tr-l
-200
tr-l
-50
E5@C Digital Temperature Controllers User's Manual (H174)
Transfer Output
Signal Type
Transfer Output
Type
pv
Transfer Output
Upper Limit
Transfer Output
Lower Limit