Cable and fiber installation
............................................................................................................................................................................................................................................................
Table 3-21 Synchronization cable (DS1 timing reference) connections
Conn.
Sync1 (J9)/
Sync2 (J14)

Office alarm cable installation

Description
Office alarms are the common method used in a central office for maintenance personnel
to quickly isolate a failure. Perform this procedure if connection to the office alarm system
is required.
Note:
capable of switching 1 amp at 50 volts, or 2 amps at 25 volts. Their ability to switch
large transient currents means that they can, if necessary, switch up to ten 5-watt aisle
pilot lamps.
If transient voltages or currents are above these limits, transient noise-suppressing devices
such as diodes or contact protection networks must be used to keep within the voltage and
current limits. If these protection devices are not sufficient, an external buffer relay MUST
be provided.
In all cases, and as a matter of good practice, suppression devices such as diodes or contact
protection networks must be provided across any external relay coil being driven by the
Alcatel-Lucent 1665 DMX high-capacity shelf to limit transient voltages and currents.
Office alarm cable assemblies are listed in
(p.
3-56).
............................................................................................................................................................................................................................................................
Alcatel-Lucent 1665 DMX R9.0
365-372-304R9.0 Issue 2
July 2010
Jacket
Color
Red
BL
W
Gray
BL
W
Drain
The office alarm relay contacts are rated at 50 VA which means that they are
9-Pin
Special
conn.
conn.
Designation
1
Rx1
RGO1/RGO2
6
Tx1
TPO1/TPO2
2
Rx2
RGI1/RGI2
7
Tx2
TPI1/TPI2
5
GND
GRD
Table 3-22, "Office alarm cable assemblies"